Addressable Zone Monitor Unit


TX7201 Addressable Zone Monitor unit is an addressable interface module, which will integrate conventional detectors or conventional manual call points to addressable system. When any of the connected devices alarms are active, the unit can send the alarm message to fire alarm controller,which generates alarm signal and displays its address. The unit can match with the conventional optical smoke detector, conventional rate of rise and fixed temperature detector and conventional manual call point etc. It has the function of checking short or open circuit of the output connection,by the End of Line Resistor (EOLR). The fault massage includes open circuit, short circuit or any removal of the detectors.

The unit manufactured base on the requirement of EN 54 part 18, European Standard. The unit is aesthetically pleasing with unobtrusive design that will complement modern building designs and its plug-in type assembles make installation and maintenance more convenient to the installer. The unit is compatible to the TX7 series  Analogue Intelligent Fire Alarm Control Panel, produced by single manufacture T&A, to avoid addressable communication compatibility problem.


Feature and Benefits

  • EN54-18 Compliance
  • Built-in MCU processor and digital addressing
  • Intelligent self-diagnosis of open circuit
  • Enhanced capacity of interference resistance by using multilevel wave filtering process
  • LED status indicator
  • Onsite Adjustable Parameter
  • Loop and external power input
  • Aesthetically pleasing design
  • Parallel connecting up to 16 conventional detector
  • Unit mounting with fix base for simple installation

Technical Specification

  • Listed                                     LPCB Pending
  • Compliance                           EN54-18:2005/AC2007
  • Input Voltage                        Loop Power:24VDC [16V to 28V]
                                                        External PSU: 20 to 28VDC
  • Current Consumption           Loop: Standby 1.3mA, Alarm: 5mA
                                                        External PSU: Standby10mA, Alarm: 60mA
  • Control output voltage         24VDC (Only for the use of TX7130, Do not allow the short circuit)
  • End of line Resistance           5.1Kohms/ ? W
  • Protocol/Addressing             T&A, Value range from 1 to 254
  • Indicator Status                     Normal: Single blink/Active: Steady/Fault: Double Blink
  • Material / Colour                   ABS / White Glossy finishing
  • Dimension / LWH                  108 mm x 86 mm x38 mm
  • Weight                                   154g (with Base), 83g (without Base)
  • Operating Temperature         -10°C to +50°C
  • Ingress Protection Rating       IP30
  • Humidity                                 0 to 95% Relative Humidity, Non condensing


Addressable Zone Monitor Module






TANDA Development Pte.Ltd
  • 6yrs
Singapore, Singapore, Singapore
Visit The Store

Non coding Detector Relay module

Get Latest Price

Send your inquiry to this supplier

-
Send Inquiry
Send Inquiry

Product Alert

Subscribe to your interested keywords. We will send freely the latest and hottest products to your Inbox. Don't miss any trade information.

版權所有 ? 寧波全貿信息技術有限公司 浙ICP備12012821號-1 浙B2-20200628