1 / 1
Basic Info
| Model No. | CFP-600L |
|---|---|
| Brand Name | TNA |
| Usage | Fire |
Product description
Conventional Fire Alarm Control Panel
The CFP-600L Series of Fire Alarm Panel uses the latest in micro-processor technology to meet today's stringent requirement for a comprehensive and versatile range of Fire Alarm Systems.
Design for ease in installation and operation,the control functions and programming are enable through a key-switch to prevent unauthorised access.
Operation of the Panel is made simple with frontal indications and switches,providing a cost effective solution for small to mid-size Fire Alarm Systems.
|
Technical Specifications :- |
|
|
Mains Voltage |
230VAC ± 15% @ 50 Hz |
|
System Operating Voltage |
24VDC ± 15% |
|
Detection Circuit Static Current |
2.4mA (Based on 20 conventional detectors) |
|
Resistance for Alarm Activation |
330? to 1.2K? |
|
End-of-Line Resistor |
4.7K? |
|
Sounder Output Circuit |
1 amp (Total Current Output) |
|
`Fire’ Output Contact |
N/O or N/C Voltage-Free Contact (Selectable) |
|
`Fault’ Output Contact |
N/O or N/C Voltage-Free Contact (Selectable) |
|
Aux. Power Output |
24VDC @ 0.5amp |
|
Operating Temperature |
-10°C to 45°C |
|
Relative Humidity |
95%, Non-Condensing |
|
IP Rating |
IP30 |
|
Packing Carton Size |
400mm x 325mm x 120mm |
|
Estimated Weight |
4.2kg (Exclude Standby Batteries) |
|
Model No. |
Zoning |
|
CFP600-L04-S |
4- Zone |
|
CFP600-L08-S |
8-Zone |
|
CFP600-L12-S |
12-Zone |
|
CFP600-L16-S |
16-Zone |
Features
2 Sounder Outputs
1 Fire Alarm Output
1 Fault Output
1 Auxiliary 24VDC Output
1 Auxiliary 24VDC Output(with Reset)