Sensitivity-50 VRMS -500 VRMS (line-to-line or line-neutral)
Frequency50 or 60 HZ Nom.(400HZ, special order)
Isolation1000 V min.
Burden--less than2.5 VA
BATTERY/DC POWER SUPPLY REQUIREMENTS (TERMINALS 8-10)
Low Voltage Range (terminals 8 and 9 connected)--10-16 V DC
High Voltage Range --14-40 V DC
Current Required--less than 200 ma
PERFORMANCE ( WITH ESD SERIES)
Capture Range-- +4% based on 3250HzOutput Voltage-- 3-7V DC
Breaker Closure Window Size--1°-25°
Relay Contact Rating(N.O. or N.C.)--10A at 28VDC
Phase Error Adjustment Range--±10°typical
there is no need to install synchronous controllers when using synchroscope so the cost of generators and machine control cabinet is reduced and the line is simplified.And what's the most important, it improves the stability of generators and machine control cabinet.